Equipment should have pre-installed brackets that can support attachment to the building as shown in Figure 124.

Step 1: Determine where to bolt the equipment
Accurately draw the bolt pattern on the wall using one of the following methods:
Masonry walls may require additional holes in equipment attachment brackets as shown on construction drawings or in the equipment manufacturer’s instructions.

ONLY USE MOUNTING BRACKETS PROVIDED. DO NOT DRILL INTO THE EQUIPMENT HOUSING.

New holes cannot be oversized or oval in shape. Repair oversized holes as shown in Figure 70.
Step 2: Install post-installed anchors
If anchoring to concrete, install post-installed anchors.
Step 3: Move the equipment into place

BE CAREFUL NOT TO DAMAGE THE ANCHORS WHEN SETTING THE EQUIPMENT.
Step 4: Attach nuts

Attach nuts to the anchor or bolt and torque according to the manufacturer’s instructions.
Piping, ductwork, and raceways may be connected.