6.6.10 Emergency Response Using Fire/HVAC Control Center

Certain operations that are managed at the Fire Control Center can play a protective role in the response to a CBR incident. Examples of such operations and how they could be used are given below.

  • Purge fans. These can be used to purge an interior CBR release or to reduce indoor contaminant concentrations following building exposure to an external CBR source. (Note: In practice, some jurisdictions may recommend purging for chemical and radiological contaminants but not for biological contaminants, which may be communicable and/or medically treatable.)
  • Communication Systems. Building communication systems that allow specific instructions to be addressed to occupants in specific zones of the building can play a significant role in directing occupant response to either an internal or external release.
  • Pressurization Fans. These provide two functions. First, the ability to override and deactivate specific positive-pressure zones may be beneficial in the event that a known CBR source is placed into such an area. Second, areas designated for positive pressurization (generally for smoke protection) may also become beneficial havens for protection from internal and external CBR releases, if they are supplied by appropriately filtered air.
  • HVAC Controls. The ability to simultaneous and individually manipulate operation of all HVAC and exhaust equipment from a single location may be very useful during a CBR event. Individuals empowered to operate such controls must be trained in their use. The provision of simple floor-by-floor schematics showing equipment locations and the locations of supply and return louvers will aid the utility of this control option.
  • Elevator Controls. Depending upon their design and operation, the ability to recall elevators to the ground floor may assist in reducing contaminant migration during a CBR event.