Double Check with Intermediate Atmospheric Vent

FIGURE 22. Double check valve with atmospheric vent.

The need to provide a compact device in ½-inch and ¾-inch pipe sizes that protects against moderate hazards, is capable of being used under constant pressure and that protects against backpressure, resulted in this unique backflow preventer. Construction is basically a double check valve having an atmospheric vent located between the two checks (See Figure 22).

Line pressure keeps the vent closed, but zero supply pressure or backsiphonage will open the inner chamber to atmosphere. With this device, extra protection is obtained through the atmospheric vent capability. Figure 23 shows a typical use of the device on a residential boiler supply line.

FIGURE 23. Typical residential use of double check with atmospheric vent.