The building shall be provided with ventilation that meets the requirements of the Florida Building Code, Residential or Florida Building Code, Mechanical, as applicable, or with other approved means of ventilation. Outdoor air intakes and exhausts shall have automatic or gravity dampers that close when the ventilation system is not operating.
Whole-house mechanical ventilation system fan efficacy.
Mechanical ventilation system fans shall meet the efficacy requirements of Table R403.5.1.
TABLE R403.5.1 MECHANICAL VENTILATION SYSTEM FAN EFFICACY
Ventilation air
Residential buildings designed to be operated at a positive indoor pressure (the air pressure inside the home is greater than the exterior air pressure) or for mechanical ventilation shall meet the following criteria:
The design air change per hour minimums for residential buildings in ASHRAE 62, Ventilation for Acceptable Indoor Air Quality, shall be the maximum rates allowed for residential applications.
No ventilation or air-conditioning system make-up air shall be provided to conditioned space from attics, crawlspaces, attached enclosed garages or outdoor spaces adjacent to swimming pools or spas.
If ventilation air is drawn from enclosed space(s), then the walls of the space(s) from which air is drawn shall be insulated to a minimum of R-11 and the ceiling shall be insulated to a,minimum of R-19, space permitting, or R-10 otherwise.