Mechanical system piping capable of carrying fluids above 105°F or below 55°F shall be insulated to a minimum of R-3. Piping insulation exposed to weather shall be protected from damage, including that caused by sunlight, moisture, equipment maintenance, and wind, and shall provide shielding from solar radiation that can cause degradation of the material. Adhesive tape shall not be permitted.