Bolts with center holes

The manufacturer provides this type of cable assembly, along with the cables, mounting bolts with holes, and brackets that attach directly to the building structure or equipment frame. Assemble the cable as shown below. Torque bolts per manufacturer’s recommendations.

Figure 151: Cable attached with bolts to bracket.

Step 1: Drill anchor holes in the building structure as required

Step 2: Attach brackets to both the building and the equipment frame

Step 3: Cut the cable to desired length and slide it through the holes in the bolts

Step 4: Tighten the cable

For rigid connections, pull the cable hand tight. Pull the cable hand-tight and let out 1/8” for vibration-isolated components. Avoid using too much tension or too much slack.

Step 5: Torque bolts

Refer to the manufacturer’s instructions.

Scroll to Top