For many connector applications in corrosion-prone buildings, using materials with enhanced corrosion resistance is the best solution for new construction, and is also recommended for replacement connectors during maintenance or repair/renovation of existing construction. The choice of alternative connector material or coating specification should be guided by the following criteria:
Recommended materials for typical residential buildings are listed in Table 3.
In Table 3, building locations are identified as oceanfront buildings, intermediate rows of buildings in corrosion-prone areas, and buildings near the coast but far enough away from the ocean that excessive corrosion is not anticipated or has not been observed. Metal connectors with minimal galvanizing on oceanfront buildings are expected to corrode at high rates. In most communities, as buildings are constructed farther from the oceanfront, the rate at which corrosion occurs should decrease significantly
at distances of 300 to 3,000 feet landward of the ocean. FEMA’s Mitigation Assessment Team deployed to Puerto Rico following Hurricanes Irma and Maria and identified areas farther inland than 3,000 feet landward of the ocean where significant corrosion was noted on exposed structural connection that would be more consistent with the corrosion experienced by buildings closer to the shoreline (FEMA, 2018b). This finding suggests that in some areas, building owners may want to consider using hot-dip galvanized or stainless steel connectors farther inland than the 3,000 feet landward of the ocean guideline.
A site survey of surrounding buildings and structures may provide information on the severity of corrosion in specific areas, which will affect the useful life of connectors and fasteners. Another key factor for material selection is the exposure class of the connectors and fasteners; exposure classes are listed in Table 3 in order of decreasing severity of corrosion at particular locations. Since access to inspect or replace connectors and fasteners is a key consideration in whether to use more corrosion-resistant materials, an assessment of the severity of corrosion in the area and exposure class may provide additional insight into whether to use upgraded fasteners and connectors.
Table 3 also includes notes on truss plate treatments based on TPI recommendations for corrosive environments. Some of the recommendations in Table 3 are based on limited research. When the severity of the exposure is unknown, selecting more corrosion-resistant materials is prudent. In most cases, a Type 304 or Type 316 stainless steel connection or fastener will provide superior corrosion resistance, as shown in the galvanic corrosion chart in Figure 7.