445 – Generators

445.6 – Listing of Stationary Generators of 600 Volts and Less

Change at a Glance:

New provisions added to require stationary generators of 600 volts and less to be listed.

445.6 Listing (Generators)

Stationary generators 600 volts and less shall be listed.
Exception: One of a kind or custom manufactured generators shall be permitted to be field labeled by a field evaluation body.
Informational Note: For additional information, see UL 2200, Standard for Stationary Engine Generator Assemblies.

445.18(D) – Emergency Shutdown in One- and Two-Family Dwelling Units

Change at a Glance:

New requirements were added to require an outdoor emergency generator shutdown device for generators (other than cord-and-plug-connected generators) installed at one- and two-family dwelling units.

445.18 Disconnecting Means and Emergency Shutdown of Prime Mover.

(A) Disconnecting Means.

(B) Emergency Shutdown of Prime Mover.

(C) Remote Emergency Shutdown.

(D) Emergency Shutdown in One- and Two-Family Dwelling Units. For other than cord-and-plug-connected portable generators, an emergency shutdown device shall be located outside the dwelling unit at a readily accessible location.

(C)(E) Generators Installed in Parallel.

(see NEC for complete text.)